Adjustment Parameters; Pulse Train Output For Meters - Toshiba Tosvert VF-AS1 Instruction Manual

The new high-performance inverter
Hide thumbs Also See for Tosvert VF-AS1:
Table of Contents

Advertisement

6.35

Adjustment parameters

6.35.1 Pulse train output for meters

 : Logic output/pulse output selection (OUT1)
 : Pulse output function selection
 : Selection of number of pulses
 Function
Pulse trains can be sent out through the OUT1-CC output terminals.
To do so, it is necessary to select a pulse output mode and specify the number of pulses.
This function output the pulse is based on  setting when each selection is suitable for the fixed
output 1 level (refer to selection 5.16).
Set the SW4 to pulse output (PULS).
Ex.) When operations frequencies (0 to 60Hz) are put out by means of 0 to 10kHz
=, =, =, =
The pulse will change between 0 and 10kHz according to the operations frequencies between 0 and 60Hz.
 See the circuit diagram shown at the bottom of page B-15.
Title
Logic output/pulse output selection

(OUT1)

Pulse output function selection

Selection of number of pulses
Note: The pulse length is fixed. Therefore, the duty is variable.
Function
:Logic output
:Pulse output
:Output frequency
:Frequency command value
:Output current
:Input voltage (DC detection)
:Output voltage
:Compensated frequency
:Speed feedback (realtime value)
:Speed feedback (1-second filter)
:Torque
:Torque command
:Torque current
:Exiting current
:PID feedback value
:Motor overload factor (OL2 data)
:Inverter overload factor (OL1 data)
:Regenerative braking resistance
:Regenerative braking resistor load
:Input power
:Output power
:Optional AI2 input
:RR/S4 input
:VI/II input
:RX input
:Optional AI1 input
:FM output
:AM output
:Fixed output 1
:Communication data output
:Fixed output 2
:Fixed output 3
:Cumulative input power
:Cumulative output power
:My function monitor 1
:My function monitor 2
:My function monitor 3
:My function monitor 4
.~. kHz
F-71
Adjustment range
overload factor (OLr data)
factor (% ED)
E6581442
Default setting
6
