Toshiba TOSVERT VF-AS3 Instruction Manual page 173

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

5. 2. 2
Setting rated frequency and rated voltage of motor
<vL: Base frequency 1>
Basic parameter
<vLv: Base frequency voltage 1>
Basic parameter
■ Function
These parameters are used to set the rated frequency and rated voltage of the motor according to
machinery. They are important parameters to decide the control range of the inverter.
■ Parameter setting
Title
Parameter name
vL
Base frequency 1
vLv
Base frequency
voltage 1
*1
Depending on the setup menu. Refer to [5. 3. 10].
The value of <VL> should be equal or smaller than that of <FH>.
■ Reference of setting
Set the rated frequency (50 Hz, 60 Hz, etc.) and rated voltage (200 V, 220 V, etc.) of the motor
according to the specifications of machinery.
The inverter is controlled based on the rating of the motor specified with these parameters.
frequency voltage 1>
Adjustment range
15.0 - 590.0
240V class: 50-330
480V class: 50-660
Output voltage (V)
<vLv: Base
0
<vL: Base frequency 1>
5-7
STOP
0.0Hz
vL
:Base frequency 1
60.0
Min: 15.0
Max: 590.0
X1000
X100
X10
STOP
0.0Hz
vLv
:Base frequency voltage 1
400
Min: 50
Max: 660
X1000
X100
X10
Unit
Default setting
Hz
*1
50.0/60.0
V
*1
Output frequency (Hz)
5. [Fundamental operation] How to use parameters
E6582062
15:25
Hz
X1
3
15:26
4
5
V
X1
9

Hide quick links: