6. 28 Pattern operation

<F520: Pattern operation>
<F521: Pattern operation continue select>
<F522: Pattern 1 repeat number>
<F523: Pattern 1 select 1> to <F530: Pattern 1 select 8>
<F531: Pattern 2 repeat number>
<F532: Pattern 2 select 1> to <F539: Pattern 2 select 8>
<F540: Operation time (1-speed)> to <F554: Operation time
(15-speed)>
■ Function
You can perform terminal run according to up to 30 types (15 types x 2 patterns) of operation
4
frequencies, operation time, and acceleration/deceleration time that were set in advance.
Pattern operation switching, and Run/Stop are all input from the terminals.
4
■ Parameter setting
6
Title
F520
F521
9
F522
F523-F530
F531
F532-F539
F540-F554
6. [Advanced] How to use parameters
Parameter name
Pattern operation
Pattern operation
continue select
Pattern 1 repeat number
Pattern 1 select 1-8
Pattern 2 repeat number
Pattern 2 select 1-8
Operation time
(1 to 15-speed)
F520 : Pattern operation
0: Disabled
1: Enabled (seconds)
2: Enabled (minutes)
Adjustment range
0: Disabled
1: Enabled (seconds)
2: Enabled (minutes)
0: Reset after stop
1: Continue after stop
1-254
255: Continuous
0: Skip
1: Sr1
2: Sr2
3: Sr3
4: Sr4
5: Sr5
6: Sr6
7: Sr7
8: F287
9: F288
10: F289
11: F290
12: F291
13: F292
14: F293
15: F294
1-254
255: Continuous
Same as <F523>
0.1-5999
6000: Continuous
6-114
E6582062
STOP
0.0Hz
13:52
Unit
Default setting
0
0
Times
1
0
Times
1
0
The
5.0
unit is
set at
<F
520>.