Toshiba TOSVERT VF-AS3 Instruction Manual page 251

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

6. 2. 2
Selecting input voltage of the terminal [RX]
<F107: Terminal RX input voltage select>
■ Function
This parameter selects the input voltage of the terminal [RX].
■ Parameter setting
Title
Parameter name
F107
Terminal RX input
voltage select
■ Difference between the settings
0: 0 to +10 V
Input 0 to 10 Vdc between the terminals [RX]-[CC].
The resolution is 1/1000 at the maximum at 0 to 10 Vdc.
1: -10 to +10 V
Input -10 to +10 Vdc between the terminals [RX]-[CC].
The resolution is 1/2000 at the maximum at -10 to +10 Vdc.
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
Reference
• Procedure to change parameter setting -> Refer to [4. 2. 3]
• Details on operation by external signals -> Refer to [Chapter 7].
F107 : Terminal RX input voltage select
0: 0 to +10V
1: -10 ∼ +10V
Adjustment range
0: 0 to +10 V
1: -10 to +10 V
6-9
E6582062
STOP
0.0Hz
12:45
Default setting
0