Graphic Operation Terminal F930GOT
6.5

ENTRY CODE

When an entry code is registered to the PLC, changes to the set values of timers and counters
in the screen mode and the monitor mode are forbidden. However, the current values can be
changed.
ENTER
Allows to register an entry code to the PLC.
This entry code is shared by other peripheral units. Enter an 8-digit (FX Series) or 6-digit (A
Series) hexadecimal number.
INPUT ENTRY CODE ¡¡¡¡¡¡¡¡
The entered entry code becomes effective when the power of the GOT is turned off, then
turned on again.
DELETE
Deletes the existing entry code. The existing entry code can be deleted only after it was
entered.
UNLOCK
Unlocks temporarily the existing entry code. (The entry code is kept registered in the PLC.)
The unlock function is valid until the power of the GOT is turned off.
Note:
When you have forgotten the existing entry code, execute "all clear" in a peripheral unit.
However, have in mind that all of the data including programs in the PLC are deleted by
"all clear". It is recommended not to forget the entry code.
u u u u Basic operation
The OTHER MODE
screen is displayed.
Paragraph 6.1
[ENTRY CODE]
[ENTRY CODE]
ENTER
DELETE
UNLOCK
ENTRY CODE
Select "ENTRY CODE"
on the screen.
Screen 1
Screen 1
[KEYBOARD]
END
A
5
0
ENTER
Enter an entry
code. Screen 2
DELETE
Enter the existing
entry code. Screen 2
UNLOCK
Unlock the existing
entry code. Screen 2
Screen 2
F
B
C
D
E
6
7
8
9
1
2
3
4
Other Mode 6
0 to F
ENT
Executes
registration.
0 to F
ENT
Executes
deletion.
0 to F
ENT
Executes
unlocking.
CLR
ENT
6-5