When the GOT is connected to the MELSEC A Series PLC via a computer link unit, the follow-
ing setting is required.
• Setting of computer link unit
Set the communication format of the computer link unit as shown below.
Table 1.4:
Used port
Mode setting switch No.
Transmission speed
Data bit
Stop bit
Parity bit
Sum check
Write during run
Station No.
The GOT station No. can be set in "SET-UP MODE". (Refer to Paragraph 2.2.)
• Caution: When RS-232C is connected
The GOT does not control CD signals. Accordingly, when the RS-232C is connected, the
buffer memory in the computer link unit should be set so that CD signals are not checked.
Example: When I/O signals in the computer link unit are 80 (H) to 9F (H)
• Restriction in functions
In connection via computer link unit, the following functions of the GOT are disabled.
- Index registers (V and Z) cannot be monitored, and their current values cannot be
changed.
- When the RS-232C is connected for communication, the printer output function of the
GOT is disabled.
- The two-port interface function is disabled.
When RS-422 is used
RS-422: Format 1
RS-232C: No-procedure
Write to buffer memory
Computer link unit connection point
X87
TO
H8
H10B
P
5
19200 bps
7 bits
1 bit
Even
Provided
Possible
00 to 0F (in accordance with setting in GOT)
K1
K1
K1: CD terminal will not be checked.
10B (H): CD terminal will be checked.
Introduction 1
When RS-232C is used
1
RS-422: No-procedure
RS-232C: Format 1
1-19