Graphic Operation Terminal F930GOT
• Restriction in device specification
1. Word specification for bit devices and bit specification for word devices are not supported
in the GOT in the same way as a case where another PLC is connected.
2. The GOT supports only the devices shown above, and does not support other devices
(that is, devices related to input image, output image, status, control, floating point and
network).
• Cautions
As described in the previous page, the user is required to set devices to be used for the
SLC500 Series. Accordingly, if devices to be monitored or set are not specified in the PLC,
a communication error may occur.
Especially, the GOT is always monitoring sampling devices in the sampling mode even if the
sampling condition is not set. As a result, a communication error occurs if sampling devices
are not present. In such a case, change sampling devices or set devices in the PLC.
Additional Functions (in V.2.00 or later) 13