Graphic Operation Terminal F930GOT
• Connection diagram
Connect the GOT to the host unit as shown below.
Host unit side
* Control lines RTS, CTS, DTR and DSR are not used.
• Communication setting
The setting related to communication can be performed using the screen creation software
or the GOT main body. (As to the screen creation software, refer to the operation manual of
the software.)
To use general-purpose communication, select "SET-UP MODE", "PLC TYPE" and "UNI-
VERSAL" in this order in the GOT main body.
To set the communication speed (baud rate), the data length, the stop bit length and the
parity, select "SET-UP MODE" and "SERIAL PORT (RS-232C)" in this order in the GOT
main body.
Set each parameter to an either available value shown below.
Table 1.15:
Baud rate
Data length
Stop bit length
Parity
FG
SD
RD
SG
19,200, 9,600, 4,800, 2,400, 1,200, 600 or 300 (bps)
8 or 7bits
1 or 2bits
Even, odd or none
5
9
4
D-sub
GOT
8
(female),
3
side
7
9-pin
2
6
1
Introduction 1
1-28