Graphic Operation Terminal F930GOT
12.2

Changeover of display screen

To changeover the display screen, perform the following setting using the screen creation soft-
ware.
12.2.1

Contents of setting

1) Changeover of the base screen (set in "Change Screen" in "Common Setting" in the screen
creation software)
Specify the screen No. of a screen to be displayed using the current value of a word device
in the PLC.
Even if the screen is not changed over from the PLC, this setting is registered in the screen
data and occupies one word device.
2) Screen changeover using a touch key (set in "Operation Setting" in "Touch Key" in the
screen creation software)
The screen is changed over when a touch key is pressed.
The screen No. of a screen be displayed can be directly specified (fixed value) or the previ-
ous screen displayed (upper hierarchy).
12.2.2

Contents of screen changeover operation

Screens are changed over as follows.
1) Changeover of the base screen
Common setting can be performed for all screens. This common setting is effective while a
user screen (No. 1 to 500) is displayed. As the initial value, the data register D0 is assigned.
When the current value of the data register D0 (initial value) or another specified register is
overwritten by a sequence program, the display screen is changed over.
2) Screen changeover using a touch key
Setting for each user screen (No. 1 to 500) can be performed.
For each screen, up to 50 touch keys can be registered.
Outline of screen changeover
F930GOT
CURRENT DISPLAY
SCREEN
(2)Screen changeover by a touch key
(fixed value or upper hierarchy)
a) The F930GOT always monitors the current value of a word device set for "1) Changeover
of the base screen", and displays a screen corresponding to the monitored current value.
b) If "2] Screen changeover using a touch key" is set, when the touch key is pressed, the
F930GOT writes automatically the fixed value (directly entered value) or the upper hier-
archy value (previously displayed screen No.) to a word device specified for "1)
Changeover of the base screen" and displays a screen corresponding to the written
value.
Creation of Display Screens (SWo o o o D5C-GOTRE-PACK) 12
PLC
(1)Word device specified
for changeover of the
base screen
(a)
Current
value
(b)
12-2