4.17 LPG SETUP USING DELTAV / AMS DEVICE MANAGER
Section 4. Configuration
The Rosemount 5900S can be setup in a F
LPG applications. DeltaV/AMS Device Manager supports configuration as
described on the following pages. Prior to performing the LPG Setup it is
recommended that you read "Preparations" on page 4-20 for information on
how to prepare a 5900S for LPG configuration.
To configure a 5900S for LPG applications:
1. Open Control Studio or some other appropriate tool for configuration of
F
fieldbus function blocks.
OUNDATION
2. Ensure that the Analog Output blocks are connected to the appropriate
devices for Vapor Temperature and Vapor Pressure.
3. In DeltaV/AMS Device Manager, open the View>Device Connection
View.
4. Double-click the FF network icon and expand the network node to view
the devices.
5. Right-click or double-click the 5900S level gauge icon to open the list of
menu options.
6. Choose the Configure option.
7. Choose Manual Setup and select the Advanced tab.
Rosemount 5900S Series
fieldbus system for
OUNDATION
4-77