F (86) (10) 6422 8586 IMPORTANT NOTICE This installation guide provides basic guidelines for Rosemount 585 Annubar. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flame-Proof, or intrinsically safe (I.S.) installations. Refer to the 585 Annubar reference manual (document number 00809-0100-4585) for more instruction.
Quick Installation Guide 00825-0200-4585, Rev AA Flanged Flo-Tap 585 Annubar January 2009 1: L OCATION AND RIENTATION Correct orientation and straight run requirements must be met for accurate and repeatable flow measurements. Refer to Table 1 for minimum pipe diameter distances from upstream disturbances.
Page 5
Quick Installation Guide 00825-0200-4585, Rev AA Flanged Flo-Tap 585 Annubar January 2009 CONTINUED Upstream Dimensions Without With Straightening Straightening Vanes Vanes Out of Plane A Plane A A’ C’ — — — — — — — — — — — —...
Page 6
Quick Installation Guide 00825-0200-4585, Rev AA Flanged Flo-Tap 585 Annubar January 2009 CONTINUED NOTE • Consult the factory for instructions regarding use in square or rectangular ducts. • “In Plane A” means the bar is in the same plane as the elbow. “Out of Plane A” means the bar is perpendicular to the plane of the elbow.
Page 7
Quick Installation Guide 00825-0200-4585, Rev AA Flanged Flo-Tap 585 Annubar January 2009 CONTINUED Vertical Orientation The sensor can be installed in any position around the circumference of the pipe provided the vents are positioned properly for bleeding or venting. Optimal results for liquid or steam are obtained when flow is up.
Page 8
Quick Installation Guide 00825-0200-4585, Rev AA Flanged Flo-Tap 585 Annubar January 2009 2: W OUNTING ARDWARE NOTE Rosemount-supplied mounting has an integral alignment built into the mounting hardware that assists in the correct drilling of the mounting hole. It also assists in the alignment of the sensor to the mounting hole for insertion.
Quick Installation Guide 00825-0200-4585, Rev AA Flanged Flo-Tap 585 Annubar January 2009 3: I NSTALL SOLATION ALVE 1. Position the isolation valve onto the mounting flange. Ensure the valve stem is positioned so that when the Flo-Tap is installed, the insertion rods will straddle the pipe and the valve handle will be centered between the rods (see Figure 7).
Page 10
Quick Installation Guide 00825-0200-4585, Rev AA Flanged Flo-Tap 585 Annubar January 2009 6: M OUNT THE NNUBAR 1. Align the flow arrow on the head with the direction of flow. 2. Use the supplied gaskets and flange bolts to fasten the Flo-Tap assembly to the isolation valve.
Page 11
Quick Installation Guide 00825-0200-4585, Rev AA Flanged Flo-Tap 585 Annubar January 2009 7: I NSERT THE NNUBAR 1. Open the isolation valve fully. 2. Rotate the crank clockwise. If a power drill with an adapter is used, do not exceed 200 revolutions per minute.
Quick Installation Guide 00825-0200-4585, Rev AA Flanged Flo-Tap 585 Annubar January 2009 8: M OUNT THE RANSMITTER Transmitter Mounting, Direct Mount Head without Valves 1. Place O-rings into grooves on the face of head. 2. Orient the equalizer valve(s) so they are easily accessible. Install a manifold with the smooth face mating to the face of the head.
Page 13
Quick Installation Guide 00825-0200-4585, Rev AA Flanged Flo-Tap 585 Annubar January 2009 CONTINUED An instrument manifold is recommended for all installations. Manifolds allow an operator to equalize the pressures prior to zeroing and isolates the process fluid from the transmitter. Figure 11.
Page 14
Quick Installation Guide 00825-0200-4585, Rev AA Flanged Flo-Tap 585 Annubar January 2009 CONTINUED Recommended Installations Gas Service Secure the transmitter above the sensor to prevent condensable liquids from collecting in the impulse piping and the DP cell. Figure 12. Vertical Line Figure 13.
Page 15
Quick Installation Guide 00825-0200-4585, Rev AA Flanged Flo-Tap 585 Annubar January 2009 Steam Service (above 450 °F (232 °C)) Mount the transmitter below the process piping. Route the impulse piping down to the transmitter and fill the system with cool water through the two tee fittings. Figure 16.
Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting our local sales office. European Pressure Equipment Directive (PED) (97/23/EC) Rosemount 585 Annubar — Refer to EC declaration of conformity for conformity assessment Pressure Transmitter — See appropriate Pressure Transmitter QIG...