Rosemount 5900S Series
6.2.9
Loading the
Default Database
6-14
The Default Database is the original factory settings of the holding register
database.
TankMaster WinSetup offers the option to load the Default Database. This
can be useful if, for example, you want to try new database settings and then
want to reload the original factory settings, or when tank conditions have been
altered. If error messages appear or other problems occur concerning the
Database a troubleshooting is recommended before loading the Default
Database.
NOTE!
The device address remains unaltered when the default database is loaded.
To load the default database
1. Select the desired device icon in the TankMaster WinSetup workspace
window.
2. Click the right mouse button and choose the View Holding Register
option.
3. Choose the All option and type 65510 in the Start Register input field.
Type the desired number of registers to be displayed in the Number of
Registers field and click the Read button.
4. Double-click in the Value (65535) field.
5. From the drop-down list, select the Reset_to _factory_setting option.
6. Click the OK button.
Reference Manual
00809-0100-5900, Rev CA
Section 6. Service and Troubleshooting
June 2014