7. Set the temperature and pressure scaling for analog inputs, enter fixed values, and
8. Select Finish to write the configuration settings to the meter.
9. Save the meter configuration file and collect a Maintenance log.
10. Disconnect from the meter using the tool bar icon,
4.2
Using AMS Device Manager to configure the
meter
This procedure assumes you have AMS Device Manager installed on the host computer
and have downloaded the latest Daniel Liquid Ultrasonic Meter Device Description (DD).
If not installed, click the link below to download the AMS device installation tool kit.
https://www.emerson.com/en-us/support/software-downloads-drivers
4.2.1
Installing AMS Device Description
Procedure
1. Use the link above to search for the Device Description (DD) for your Daniel 3810
2. Use the pull-down menu and select the Brand/Manufacturer - Emerson Daniel
3. Next select the Device, Liquid 3810 Series from the pull-down menu.
4. Choose the Device Revision1, from the pull-down menu.
5. Next, select HART from the Communication Protocol menu.
6. Select AMS Device Manager for the Host System.
7. Select the Host System Revision 11.5.
8. Verify your search parameters are correct, as shown below.
Installation manual
set alarm limits for both.
menu path and close the Daniel MeterLink application and prepare to seal the
meter.
Series Liquid Ultrasonic Flow Meter.
Industries.
Configuration
May 2019
, or the Meter → Diconnect