Section 6. Service and Troubleshooting
6. Repeat for each 5900S gauge to be programmed.
Use the Remove button if you wish to change the list of devices to be
programmed.
7. Click the Browse button to locate the flash program file. File extension
*.cry are used for these files.
8. Click the Start Programming button. Now the Start Device
Programming window appears.
9. Click the Start Programming button to activate device programming.
If a 2160 Field Communication Unit (FCU) is used, a maximum of 25
devices can be programmed. If there are more devices the programming
must be divided in two steps.
10. Update the TankMaster installation by adding the new *.ini files for the
5900S gauge to the TankMaster installation folder.
Two *.ini files are used for the 5900S, RLG.ini and RLG0xx.ini, where
xx is the identification code of the 5900S gauge application software.
The RLG.ini file is copied to the C:\Program Files\Rosemount\Server
folder.
The RLG0xx.ini file is copied to the C:\Program Files\Rosemount\Shared
folder.