Rosemount 5900S Series
C-12
16
LEVEL
17
LENGTH_UNIT
18
LEVEL_RATE
19
LEVEL_RATE_UNIT
20
ENV_DEVICE_MODE
21
DIAGN_DEVICE_ALERT
22
DEVICE_VERSION_NUMBER
23
DIAGN_REVISION
24
SERIAL_NO
25
STATS_ATTEMPTS
26
STATS_FAILURES
27
STATS_TIMEOUTS
28
FF_DEVICE_NUMBER
29
FF_WRITE_PROTECT
30
P1451_SLAVE_STATS
31
P1451_HOST_STATS
32
DISTANCE
33
SIGNAL_STRENGTH
34
SIGNAL_STRENGTH_UNI
35
ANTENNA_TYPE
36
TCL
37
PIPE_DIAMETER
38
HOLD_OFF_DIST
39
ANTENNA_SIZE
40
OFFSET_DIST_G
41
TANK_HEIGHT_R
42
BOTTOM_OFFSET_DIST_C
43
CALIBRATION_DIST
44
TANK_SHAPE
Distance from the zero level (tank bottom) to the
product surface
Length Unit
Velocity at which the product surface is moving
Level Rate Unit
Service Mode (see Table C-5)
Errors and warnings for 2410 Tank Hub usage.
See Table C-14 on page C-16.
PM card SW version number
PM revision
Main Label Device ID
Total number of messages sent to PM
Total number of failed messages to PM
Total number of timed-out messages to PM
CM board serial number
CM board write protection status
Communication statistics
Communication statistics
Distance from the tank reference point (normally
the lower side of the flange) to the product
surface
Amplitude of the echo from the product surface.
A high value indicates a good reflection by the
surface
Signal strength unit
Antenna type on the device (see Table C-6)
Tank Connection Length. Electrical distance
between the transmitter's reference point and the
microwave unit. Only for user defined antennas.
Still-pipe inner diameter, see "Tank Geometry" on
page 4-6.
Hold Off Distance defines how close to the
gauge's reference point a level measurement is
accepted, see "Tank Geometry" on page 4-6.
Still-pipe Array antenna size
Gauge Reference Distance (G), see "Tank
Geometry" on page 4-6. Use the Distance Offset
(G) if a reference point other than the lower side
of the device flange is required.
Tank Reference Height (R) is defined as the
distance between the upper reference point and
the lower reference point (zero level). See "Tank
Geometry" on page 4-6.
Minimum Level Offset (C) defines a lower null
zone which extends the measurement range
beyond the Zero Level Reference Point down to
the tank bottom. See "Tank Geometry" on
page 4-6.
Calibration Distance is by default set to zero. It is
used to adjust the level measurement so that
measured levels match hand dipped levels. See
"Tank Geometry" on page 4-6.
Tank Type (see "Tank Shape" on page 4-15 and
Table C-8). Optimizes the 5900S for various tank
geometries.
Appendix C. F
OUNDATION
Reference Manual
00809-0100-5900, Rev CA
June 2014
Fieldbus Block Information