3.4.12 Wiring Diagrams

Figure 3-28. 5900S wiring
diagram
TankMaster PC
3-52
The standard version of the Rosemount 5900S has a single intrinsically safe
fieldbus input. The 5900S has a built-in termination by short-circuiting the X2
connector.
An intrinsically safe output on connector X4 can be used for "daisy-chain"
connection to other devices in a Raptor system.
Connector X3 is used for a fieldbus input/output cable shield connection
(separated from chassis ground).
Figure 3-28 illustrates a typical wiring diagram with a Rosemount 5900S
Radar Level Gauge connected to a Rosemount 2240S Multi-input
Temperature Transmitter. In this example the termination is enabled in the
2240S transmitter which is the last device on the Tankbus (see "The Raptor
Tankbus" on page 3-43).
In case you prefer to connect the 2240S to the 2410 Tank Hub, you may
"daisy-chain" the 5900S to the 2240S, and terminate the Tankbus by a jumper
in terminal X2 on the 5900S terminal block.
Field Communicator
Rosemount 2410 Tank Hub
Power supply
See also "Terminal Blocks" on page 3-49 for information on terminal block
connections.
ROSEMOUNT 5900S
RADAR LEVEL GAUGE
Tankbus
Rosemount 2240S Multi-input
Temperature Transmitter with
built-in terminator
Reference Manual
00809-0100-5900, Rev CA
June 2014
Shield