Rosemount 5900S Series
F
™ fieldbus characteristics
OUNDATION
Polarity sensitive
Quiescent current draw
Lift-off minimum voltage
Device capacitance / inductance
Class (Basic or Link Master)
Number of available VCRs
Links
Minimum slot time / maximum response delay
/ minimum intermessage delay
Blocks and
Execution time
Instantiation
Conforming F
™ fieldbus
OUNDATION
PlantWeb alert support
Action support wizards
Advanced diagnostics
Electric
Tankbus cabling
Power supply
Bus current draw
Microwave output power
Mechanical
Housing material & surface treatment
Cable entry (connection/glands)
Dimensions
Total weight
A-2
No
51 mA
9.0 VDC
See Appendix B: Product Certifications
Link Master (LAS)
Maximum 20, including one fixed
Maximum 40
8 /5 /8
1 Resource block
5 Transducer blocks (Level, Register, Adv_Config, Volume, and LPG)
6 Analog Input (AI) blocks: 10 ms , 2 Analog Output (AO) blocks: 10 ms
1 Proportional/Integral/Derivate (PID) block: 15 ms
1 Signal Characterizer (SGCR) block: 10 ms, 1 Integrator (INT) block: 10 ms,
1 Arithmetic (ARTH) block: 10 ms, 1 Input Selector (ISEL) block: 10 ms
1 Control Selector (CS) block: 10 ms, 1 Output Splitter (OS) block: 10 ms
For more information, see the F
00809-0100-4783)
Yes
ITK 5.2
Yes
Restart measurement, write protect device, factory reset - measurement configuration,
start/stop device simulation, set as surface, reset statistics, change all modes,
register/remove false echo, refresh echo peaks, pin verification, change vapor pressure,
change vapor temperature
Software, memory/database, electronics, internal communication, simulation, level
correction, level measurement, ambient temperature, vapor pressure/temperature
correction, LPG verification pin, and manual measurement values
2
0.5-1.5 mm
(AWG 22-16), twisted shielded pairs
Input voltage U
for FOUNDATION™ fieldbus:
i
• 9.0 to 32 VDC
• 9.0 to 17.5 VDC in FISCO applications
• 9.0 to 30 VDC in I.S. applications
See Appendix B: Product Certifications for information on FISCO and Entity parameters.
See also "Typical installation" on page 3-44.
50 mA (100 mA for the 2-in-1 version)
< 1 mW (see also Raptor Technical Description)
Polyurethane-coated die-cast aluminum
Two ½ - 14 NPT entries for cable glands or conduits. One metal plug to seal any unused
port is enclosed in the transmitter delivery.
Optional:
• M20 x 1.5 conduit / cable adapter
• Cable glands in metal (½ - 14 NPT)
• 4-pin male Eurofast connector or A size Mini 4-pin male Minifast connector
See "Dimensional Drawings" on page A-5
5900S transmitter head: 5.1 kg (11.2 lbs) for the single version and 5.4 kg (11.9 lbs) for
the 2-in-1 version
5900S with horn antenna: Appr. 12 kg (26 lbs)
5900S with parabolic antenna: Appr. 17 kg (37 lbs)
5900S with still-pipe array antenna: Appr. 13.5-24 kg (30-53 lbs)
5900S with LPG/LNG antenna: Appr. 30 kg (66 lbs) for 6-in. 150 psi, and 40 kg (88 lbs)
for 6-in. 300 psi