Table 5 - Opto-isolated Input Terminals
4.2.8

Output Relays

This test checks that all the output relays are functioning correctly. The P442 relays have 21
output relays and the P444 relays have 32 output relays.
Ensure that the relay is still in test mode by viewing cell [0F0E: COMMISSIONING TESTS,
Test Mode].
The output relays should be energised one at a time. To select output relay 1 for testing, set
cell [0F0F: COMMISSIONING TESTS, Test Pattern] as shown in Table 6.
Connect a continuity tester across the terminals corresponding to output relay 1 given in
Table 6.
To operate the output relay set cell [0F11: COMMISSIONING TESTS, Contact Test] to
'Apply Test'. Operation will be confirmed by the continuity tester operating for a normally
open contact and ceasing to operate for a normally closed contact.
Reset the output relay by setting cell [0F11: COMMISSIONING TESTS, Contact Test] to
'Remove Test'.
Note:
Repeat the test for all the other output relays (number depends on the model).
MiCOM P442
Output
N/C
Without high break relay board (all models except P442×××C)
Relay 1
Relay 2
Relay 3
Apply field voltage to terminals
P442
-ve
D15
E1
E3
E5
E7
E9
E11
E13
E15
Ensure that thermal ratings of anything connected to the output relays during the
contact test procedure are not exceeded by the associated output relay being
operated for too long. It is therefore advised that the time between application and
removal of contact test be kept to the minimum.
N/O
-
H1-H2
-
H3-H4
-
H5-H6
MiCOM P40 Agile P442, P444
P444
+ve
-ve
D16
D15
E2
E1
E4
E3
E6
E5
E8
E7
E10
E9
E12
E11
E14
E13
E16
E15
F1
F3
F5
F7
F9
F11
F13
F15
Output
N/C
Relay 12
G10-G12
Relay 13
G13-G15
Relay 14
G16-G18
Commissioning
+ve
D16
E2
E4
E6
E8
E10
E12
E14
E16
F2
F4
F6
F8
F10
F12
F14
F16
N/O
G11-G12
G14-G15
G17-G18

Advertisement

Table of Contents
loading

This manual is also suitable for:

P442P444

Table of Contents