Autorecloser (“Autoreclose” Menu) - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Setting
MiCOM P40 Agile P442, P444
Menu text
GROUP 1 – SYSTEM CHECK
C/S Check Scheme for Man
CB
Check synchronism scheme for Manual CB Closure. At least, one condition must be
selected to activate the synchronism check logic. The Dead Bus / Dead Line can only be
created using PSL.
The check synchronism condition is only taken into account if a SOTF condition has been
enabled. Otherwise, a dedicated PSL can be created using DDB (live line or live bus/dead
line) – live/live cannot be managed – in that case.
V< Dead Line
V> Live Line
V< Dead Bus
V> Live Bus
The Live Line and Dead Line settings define the thresholds which dictate whether or not the
line or bus is determined as being live or dead by the relay logic.
Diff Voltage
Differential voltage between Line VT and Busbar VT measurements.
Diff Frequency
Differential frequency between Line VT and Busbar VT measurements.
Diff Phase
Differential voltage between Line VT and Busbar VT measurements.
Bus-Line Delay
Bus Line time delay: The Check synchronism is not verified when 'V> Live Bus', 'V> Live
Line', 'Diff Voltage', 'Diff Frequency' or 'Diff Phase' threshold is exceeded for longer than
'Bus-Line delay' time-delay.
3.17
Autorecloser ("autoreclose" menu)
Menu text
GROUP 1 – AUTORECLOSE
The 'A/R TPAR Enable' or 'A/R SPAR Enable' opto inputs (assigned in the PSL) have
priority and enables or disables the single or three poles autoreclose function.
Otherwise, set 'A/R Single Pole' and 'A/R Three pole' ('CB Control' menu) to enable
Autoreclose.
AUTORECLOSE MODE
Default setting
111
Bit 0: Live Bus / Dead Line,
Bit 1: Dead Bus / Live Line,
Bit 2: Live Bus / Live Line.
13V
5V
32V
30V
13V
5V
32V
30V
6.5V
0.5V
0.05Hz
0.02Hz
20°
0.2s
0.1s
Default setting
P44x/EN ST/Hb6
Setting range
Min
Max
30V
120V
30V
120V
40V
1Hz
90°
2s
Setting range
Min
Max
(ST) 4-67
Step size
1V
1V
1V
1V
0.1V
0.01Hz
2.5°
0.1s
Step size