Non-Protection Features - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P44x/EN AP/Hb6
(AP) 5-8
element can be used for SOFT/TOR logic. The fourth element can be configured for
stub bus protection in 1½ circuit breaker arrangements.
• 50N/51N: Instantaneous and time-delayed neutral overcurrent protection. Four
elements are available.
• 67N: Directional earth fault protection (DEF) - This can be configured for channel
aided protection, plus two elements are available for backup DEF.
• 67 / 46: Directional or non-directional negative sequence overcurrent protection - This
element can provide backup protection for many unbalanced fault conditions.
• 32N: Maximum of Residual Power Protection - Zero sequence Power Protection This
element provides protection against high resistance faults, cleared without using a
communications channel.
• 27 / 59: Undervoltage and overvoltage protections - Four-stage, configurable as either
phase to phase or phase to neutral measuring. Stage 1 may be selected as either
Inverse Definite Minimum Time (IDMT) or Definite Time (DT) and stage 2 is DT only.
• 37: Undercurrent Protection – this element consists of two independ stages protection,
with two independent time-delay setting.
• 81U / 81O: Underfrequency and overfrequency protection – This element can provides
a four-stage time-delayed underfrequency protection and two-stage time-delayed
overfrequency protection.
• 49: Thermal overload Protection - with dual time constant. This element provides
separate alarm and trip thresholds.
• 50 / 27: Switch on to fault (SOTF) and Trip On Reclose (TOR) protections - These
settings enhance the protection applied for manual circuit breaker closure.
• 78 / 68: Power swing blocking - Selective blocking of distance protection zones
ensures stability during the power swings experienced on sub-transmission and
transmission systems (stable swing or Out of Step condition = loss of synchronism).
The relay can differentiate between a stable power swing and a loss of synchronism
(out-of-step).
• 85: Channel Aided schemes with basic schemes, Permissive Underreach (PUP) and
Permissive Overreach (POP) transfer trip schemes and Blocking schemes.
• Weak infeed echo logic.
• Accelerated Trip features (Loss of Load – Zx extension).
• 46 BC: Broken conductor detection - To detect network faults such as open circuits,
where a conductor may be broken but not in contact with another conductor or the
earth.
• 50 BF: Circuit breaker failure protection - Generally set to backtrip upstream circuit
breakers, should the circuit breaker at the protected terminal fail to trip. Two stages
are provided.
• VTS: Voltage transformer supervision (VTS). - To detect VT fuse failures. This
prevents maloperation of voltage dependent protection on AC voltage input failure.
• CTS: Current transformer supervision - To raise an alarm should one or more of the
connections from the phase CTs become faulty.
• CVTS: Capacitive Voltage Transformer Supervision – to supervise voltage divider
capacitors supervision when residual voltage is greater than the set value.
1.2.2

Non-Protection Features

The P442 and P444 relays have the following non-protection features:
• 79/25: Autoreclosure with Check synchronism - This permits up to 4 reclose shots,
with voltage synchronism, differential voltage, live line/dead bus, and dead bus/live
line interlocking available. Check synchronism is optional.
• Measurements - Selected measurement values polled at the line/cable terminal,
available for display on the relay or accessed from the serial communications facility.
Application Notes
MiCOM P40 Agile P442, P444

Advertisement

Table of Contents
loading

This manual is also suitable for:

P442P444

Table of Contents