GE MiCOM P40 Agile Technical Manual page 355

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Programmable Logic
MiCOM 40 Agile P442, P444
Ordinal
English Text
1038
BAR
469
Battery Fail
1041
BLK Protection
330
Brk.Conduct.Trip
202
Brok. Cond. Alarm
338
CB Aux A
1025
CB Aux A (52-A)
1026
CB Aux A (52-B)
339
CB Aux B
1027
CB Aux B (52-A)
1028
CB Aux B (52-B)
340
CB Aux C
1029
CB Aux C (52-A)
1030
CB Aux C (52-B)
1045
CB Discrepancy
179
CB Fail Alarm
Description
Block internal autoreclose: Block Autoreclose (via an
opto input or in the PSL).
The DDB:'BAR' input will block the autoreclosure and
lockout the autoreclose if a cycle is in progress. If a
single-pole cycle is in progress a three-pole trip will be
issued and the autorecloser will lock out. It can be
used when protection operation is required without
autoreclose. A typical example is for a transformer
feeder, where autoreclosing may be initiated by the
feeder's protection relay but blocked by the
transformer's protection relay. Similarly, where a circuit
breaker low gas pressure or loss of vacuum alarm
occurs during the dead time, autoreclosure should be
blocked – and BAR can be used to perform this
blocking logic.
Alarm battery fail
Block all protection functions
(21/67N/50/51/...)
Broken conductor trip
Broken Conductor Alarm
CB Phase A status (from internal logic and CBAux opto
inputs state: 1 = CB-Pole A is open.
This signal is used for Any Pole Dead & All Pole Dead
internal detection.
Circuit breaker pole A closed
(status input from CB, 52-A = normally open)
Circuit breaker pole A open
(Status input from CB, 52-B = normally closed)
CB Phase B status (from internal logic and CBAux opto
inputs state: 1 = CB-Pole B is open.
This signal is used for Any Pole Dead & All Pole Dead
internal detection.
Circuit breaker pole B closed
(status input from CB, 52-A = normally open)
Circuit breaker pole B open
(Status input from CB, 52-B = normally closed)
CB Phase C status (from internal logic and CBAux
opto inputs state: 1 = CB-Pole C is open.
This signal is used for Any Pole Dead & All Pole Dead
internal detection.
Circuit breaker pole C closed
(status input from CB, 52-A = normally open)
Circuit breaker pole C open
(Status input from CB, 52-B = normally closed)
CB Discrepancy (one pole open).
If it is assigned to an opto input in the PSL and
energised, the DDB:'CB Discrepancy' signal will inform
the protection of a pole discrepancy status (one pole
opened and the other two poles closed). It must be set
to high logical level before Dead time 1 has elapsed –
it can also be generated internally (see Cbaux logic).
Circuit breaker failure on any trip
P44x/EN PL/Hb6
(PL) 6-35
Source
PSL (IN)
Autorecloser
PSL(OUT)
PSL (IN) All
protection
PSL (OUT)
Broken Cond.
PSL(OUT)
Broken
conductor
PSL (OUT)
CB status
PSL (IN)
CB STATUS
PSL (IN)
CB STATUS
PSL (OUT)
CB status
PSL (IN)
CB STATUS
PSL (IN)
CB STATUS
PSL (OUT)
CB status
PSL (IN)
CB STATUS
PSL (IN)
CB STATUS
PSL (IN) CB
Status
PSL (OUT)
Breaker Fail