Block Autoreclose Logic - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Application Notes
MiCOM P40 Agile P442, P444
When autoreclosure is not required for multiphase faults, DDB signals '2Ph Fault' and '3Ph
Fault' can be mapped via the PSL in a logic OR combination onto input DDB: 'BAR' (Block
internal AutoReclose, section 5.9.1.5). When blocking is only required for a three phase fault,
the DDB signal '3Ph Fault' is mapped to 'BAR' alone. Three phase faults are more likely to
be persistent, so many utilities may not wish to initiate autoreclose in such instances.
The next diagram shows the block autoreclose logic.
bit
setting
Autoreclose lockout / Block A/R
00
At T2
01
At T3
02
At Tzp
03
LoL Trip
04
I>1 Trip
05
I>2 Trip
06
V<1 Trip
07
V<2 Trip
08
V>1 Trip
09
V>2 trip
0A
IN>1 Trip
0B
IN>2 Trip
0C
Aided D.E.F
Trip
0D
Zero. Seq.
Power Trip
0E
IN>3 Trip
0F
IN>4 Trip
10
PAP Trip
Figure 119: Block autoreclose logic
DDB
bit
T2
11
T3
12
tZp
13
Loss. Load Trip
14
I>1 Trip
15
I>2 Trip
16
V<1 Trip
17
V<2 Trip
18
V>1 Trip
19
V>2 Trip
1A
IN>1 Trip
1B
IN>2 Trip
1C
DEF Trip A C
1D
OR DEF Trip B
1E
OR DEF Trip C
Autoreclose lockout / Block A/R 2
ZSP Trip
00
01
IN>3 Trip
02
IN>4 Trip
03
PAP Trip A
05
OR PAP Trip B
OR PAP Trip C
setting
DDB
Thermal Trip
Trip Thermal
I2>1 Trip
I2> Trip
I2>2 Trip
I2>2 Trip
I2>3 Trip
I2>3 Trip
I2>4 Trip
I2>4 Trip
VN>1 Trip
VN>1 Trip
VN>2 Trip
VN>2 Trip
At Tzq
tZq
V<3 Trip
V<3 Trip
V<4 Trip
V<4 Trip
V>3 Trip
V>3 Trip
V>4 trip
V>4 trip
I<1 Trip
I<1 Block
I<2 Trip
I<2 Block
F<1 Trip
F<1 Trip
F<2 Trip
F<2 Trip
F<3 Trip
F<3 Trip
F<4 Trip
F<4 Trip
F>2 Trip
F>2 Trip
P44x/EN AP/Hb6
(AP) 5-157