GE MiCOM P40 Agile Technical Manual page 357

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Programmable Logic
MiCOM 40 Agile P442, P444
Ordinal
English Text
178
CT Fail Alarm
241
Ctrl Cls In Prog
203
CVT Alarm
274
DEF Fwd
273
DEF Rev
271
DEF Sig. Send
275
DEF Start A
276
DEF Start B
277
DEF Start C
1060
DEF Timer Block
278
DEF Trip A
279
DEF Trip B
280
DEF Trip C
272
DEF UNB CR
1050
DEF. Chan Recv
1052
DEF. COS
345
DIST Convergency
244
DIST Fwd
Description
Current transformers supervision indication: Indicates a
CT Fail detected after time delay has elapsed is issued
Manual (control) close in progress - using CB control
(time-delay manual closing delay in progress).
Alarm for capacitive voltage Transformer: Indicates the
residual voltage is greater than the threshold adjusted
in the settings, during a time-delay greater than the
adjustment. That alarm is also included in the general
alarm.
Channel Aided DEF: forward fault
Channel Aided DEF: reverse fault
DEF protection schemes - Signal Send
(Default PSL: Relay 05)
Channel Aided DEF: start phase A
Channel Aided DEF: start phase B
Channel Aided DEF: start phase C
Block aided DEF time delay
The DEF time-delay will be blocked & DEF will start but
will not issue any trip command.
Reset to 0: Opto input power off if signal assigned to
an opto input OR DDB at 0 if signal assigned to a DDB
cell
Channel Aided DEF: trip phase A
Default PSL: Relay 09
Channel Aided DEF: trip phase B
Default PSL: Relay 09
Channel Aided DEF: trip phase C
Default PSL: Relay 09
Unblocking DEF channel
internal Carrier Received signal (main Directional Earth
Fault unblocking signal) received.
Signal received on main channel for DEF scheme logic
(depending on settings: Aided DEF/Scheme logic)
Selected as shared by default – Can operate as an
independent scheme with a separate opto input from
Dist
Default PSL: Opto Label 1
DEF scheme channel out of service / Loss of Guard
Selected shared by default – Can operate as an
independent scheme with a different opto input from
Dist
Default PSL: Opto Label 2
Distance protection: Internal characteristic
Set to 1: logic with Distance Start at 1 (Minimum 1 loop
has been detected in the quadrilateral characteristic)
Set to 0: Reset of (R, X) (resistance, reactance)
calculation made by the All pole Dead detection
Distance protection: Forward fault detected (default
PSL: LED6)
Set to 1: Directional Forward detected in distance
algorithms (Deltas or Conventional) AND (Distance
Start)
Set to 0: With reset of Any Start/Dist Start
P44x/EN PL/Hb6
(PL) 6-37
Source
PSL (OUT)
CT
Supervision
PSL (OUT)
CB Control
PSL (OUT)
PSL (OUT)
Aided DEF
PSL (OUT)
Aided DEF
PSL (OUT)
Aided DEF
PSL (OUT)
Aided DEF
PSL (OUT)
Aided DEF
PSL (OUT)
Aided DEF
PSL (IN) DEF
PSL (OUT)
Aided DEF
PSL (OUT)
Aided DEF
PSL (OUT)
Aided DEF
PSL (OUT)
Unblocking
logic
PSL (IN) Un-
blocking logic
PSL (IN) Un-
blocking logic
PSL (OUT)
Distance
PSL (OUT)
Distance

Advertisement

Table of Contents
loading

This manual is also suitable for:

P442P444

Table of Contents