Programmable Logic
MiCOM 40 Agile P442, P444
1.2.3
Programmable LED output mapping
The default mappings for each of the programmable LEDs are as shown in the following
table:
LED
P442 Relay
No.
1
Any Trip A
2
Any Trip B
3
Any Trip C
4
Any Start
5
Z1+Aided Trip
6
Dist Fwd
7
Dist Rev
8
A/R Enable
Note:
1.2.4
Fault recorder trigger
The default PSL trigger which initiates a fault record is shown in the following table:
P442 Relay
Any Start
Any Trip
If the fault recorder trigger is not assigned in the PSL, no Fault recorder can be initiated and
displayed in the list by the LCD front panel.
P444 Relay
Any Trip A
Any Trip B
Any Trip C
Any Start
Z1+Aided Trip
Dist Fwd
Dist Rev
A/R Enable
All the LEDs are latched in the default PSL.
P444 Relay
Any Start
Any Trip