GE MiCOM P40 Agile Technical Manual page 373

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Programmable Logic
MiCOM 40 Agile P442, P444
Ordinal
English Text
398
V<3 Start A
399
V<3 Start B
400
V<3 Start C
1071
V<3 Timer Block
404
V<3 Trip
397
V<4 Start
401
V<4 Start A
402
V<4 Start B
403
V<4 Start C
1072
V<4 Timer Block
405
V<4 Trip
240
V> Live Bus
238
V> Live Line
292
V> Start Any A
293
V> Start Any B
294
V> Start Any C
199
V>1 Alarm
295
V>1 Start
377
V>1 Start A
378
V>1 Start B
379
V>1 Start C
1073
V>1 Timer Block
297
V>1 Trip
200
V>2 Alarm
296
V>2 Start
380
V>2 Start A
381
V>2 Start B
382
V>2 Start C
Description
Undervoltage phase A stage 3 start
Undervoltage phase B stage 3 start
Undervoltage phase C stage 3 start
Block phase undervoltage stage 3 time delay
Set to 1: 'V<3 Time Delay' will be blocked and V<1 will
start but will not issue any trip command.
Reset to 0: Opto input power off if signal assigned to
an opto input OR DDB at 0 if signal assigned to a DDB
cell
Undervoltage stage 3 trip
Undervoltage stage 4 start
Undervoltage phase A stage 4 start
Undervoltage phase B stage 4 start
Undervoltage phase C stage 4 start
Block phase undervoltage stage 4 time delay
Set to 1: 'V<4 Time Delay' will be blocked and V<1 will
start but will not issue any trip command.
Reset to 0: Opto input power off if signal assigned to
an opto input OR DDB at 0 if signal assigned to a DDB
cell
Undervoltage stage 4 trip
Live Bus: high when the Live Bus condition is met
(voltage above the V>Live Bus threshold value
(setting) - always calculated as a single phase voltage
reference.
Live Line: high when the Live line condition is met
(voltage above the 'V> Live Line' threshold value
(setting) - always calculated as a single phase voltage
reference.
Any overvoltage start detected on phase A
Any overvoltage start detected on phase B
Any overvoltage start detected on phase C
1st stage overvoltage alarm picks up when V>1 starts
st
Overvoltage function 1
stage start for any phase
Overvoltage stage 1 pick up on phase A
Overvoltage stage 1 pick up on phase B
Overvoltage stage 1 pick up on phase C
Block phase overvoltage stage 1 time delay
Set to 1: 'V>1 Time Delay will be blocked and V>1 will
start but will not issue any trip command.
Reset to 0: Opto input power off if signal assigned to
an opto input OR DDB at 0 if signal assigned to a DDB
cell
st
Overvoltage 1
stage 3-phase trip
2nd stage overvoltage alarm picks up when V>2 starts
nd
Overvoltage function 2
stage start for any phase
Overvoltage stage 2 pick up on phase A
Overvoltage stage 2 pick up on phase B
Overvoltage stage 2 pick up on phase C
P44x/EN PL/Hb6
(PL) 6-53
Source
PSL
PSL
PSL
PSL (IN) V<3
PSL
PSL
PSL
PSL
PSL
PSL (IN) V<4
PSL
PSL (OUT)
Synchro
Check
PSL (OUT)
Synchro
Check
PSl (OUT)
Overvoltage
PSl (OUT)
Overvoltage
PSl (OUT)
Overvoltage
PSL (OUT)
V>1
PSl (OUT)
Overvoltage
PSL
PSL
PSL
PSL (IN) V>1
PSl (OUT)
Overvoltage
PSL (OUT)
V>2
PSl (OUT)
Overvoltage
PSL
PSL
PSL