Programmable Logic
MiCOM 40 Agile P442, P444
Ordinal
English Text
313
TOR Enable
314
TOC Start A
315
TOC Start B
316
TOC Start C
317
Any start
318
1ph Fault
319
2ph Fault
320
3ph Fault
321
Any Trip
322
Any Int. Trip A
323
Any Int. Trip B
324
Any Int. Trip C
325
Any Trip A
326
Any Trip B
327
Any Trip C
328
1P Trip
329
3P Trip
330
Brk.Conduct.Trip
331
Loss. Load Trip
332
SOTF/TOR Trip
333
tBF1 Trip
334
tBF2 Trip
335
Control Trip
Description
Trip On Reclose enable: indicates the TOR logic is
activated in the relay
Set to 1= 500 ms pulse initiated by:
'I A/R Reclaim' (internal) OR 'A/R reclaim' (External
Input)
OR Any pole open for more than 200 ms
Reset 500 ms after Any pole dead stops
Trip on Close start on phase A: indicates a trip order on
phase A has been issued by the SOTF level detectors
(Pickup time-delay = 20 ms)
Trip on Close start on phase B: indicates a trip order on
phase B has been issued by the SOTF level detectors
(Pickup time-delay = 20ms)
Trip on Close start on phase C: indicates a trip order on
phase C has been issued by the SOTF level detectors
(Pickup time-delay = 20 ms)
Any protection start logic with any phase
Default PSL: LED 4, Relay 06
(Fault record trigger in default PSL with 20 ms Dwell
Timer)
Single phase fault
Two phase fault
Three phase fault
Single or three pole trip or external protection trip
Default PSL: Relay 07
Any internal protection A phase trip
Default PSL: LED 1, Relay 02
Any internal protection B phase trip
Default PSL: LED 2, Relay 03
Any internal protection C phase trip
Default PSL: LED 3, Relay 04
Any trip A (internal or external protection)
Any trip B (internal or external protection)
Any trip C (internal or external protection)
Single pole trip (internal or external)
Three pole trip (internal or external)
Broken conductor trip
Loss of load trip (in application without communication
scheme and a 3P Trip logic)
Switch on to fault trip or trip on reclose: indicates that a
3-pole trip order has been issued by the TOR or SOTF
logic
Circuit Breaker failure on any trip, delayed by "CB Fail 1
Timer" (setting in "CB Fail" logic)
Circuit Breaker failure on any trip, delayed by "CB Fail 2
Timer" (setting in "CB Fail" logic)
Control trip command from user (by internal CB control)
P44x/EN PL/Hb6
(PL) 6-15
Source
PSL (OUT)
TOR
PSL (OUT)
SOTF
PSL (OUT)
SOTF
PSL (OUT)
SOTF
PSL (OUT)
All protection
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
All protection
PSL (OUT)
All protection
PSL (OUT)
All protection
PSL (OUT)
All protection
PSL (OUT)
All protection
PSL (OUT)
All protection
PSL (OUT)
All protection
PSL (OUT)
All protection
PSL (OUT)
All protection
PSL (OUT)
Broken Cond.
PSL (OUT)
Loss of load
PSL (OUT)
SOTF
PSL (OUT)
Breaker
failure
PSL (OUT)
Breaker
failure
PSL (OUT)
CB control