Logic Of The Distance Protection By Zones - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Application Notes
MiCOM P40 Agile P442, P444
Figure 53: logic of the distance protection by zones
Where:
Unblock PS Z1, Z2, Z3, Z4, Zp or Zq: Unblocking of Zone 1 (Z1), Z2, Z3, Z4, Zp or Zq during a
DDB: Z1,Z1x, Z2, Z3, Z4, Zp, Zq:
The fault detection is modified when the following conditions are met:
• Power swing detection (in this case, power swing detected or unblocking during a
power swing),
• Blocking logic settings during power swing,
• Type of teleprotection scheme.
When zones are blocked during the power swing, those can be unblocked by:
• Start of unblocking logic,
• Unblocking logic enabled for the concerned zone or all zones (setting).
power swing ('Power swing / Blocking zone' menu)
0 => Zx blocked during power swing
1 => Zx unblocked during power swing
Fault detected in zone 1, Z1x, 2, 3, 4, p or q and filtered
by blocking/unblocking Power Swing
P44x/EN AP/Hb6
(AP) 5-79