Hardware / Software-Version
MiCOM P40 Agile P442, P444
Software
Hardware
Model
version
version
number
Branch C3.x : Idem C2.x with new communication protocol (IEC 61850-8-1) / UCA2 not supported – Model J only (Dual optos managed by default)
C3.7
31
C3.8
31
J
C3.9
31
for P441
for P442
C3.10
31
for P444
C3.11
31
to C3.16
C3.18_A
31
Note 1:
Version C3.7 not distributed
Relay type: P441, P442, P444
Date of
issue
Add IEC 61850-8-1 protocol / Zone reset&overlap/ WeakInfeed Echo+DEF/
12/2006
Control Inp/ 2nd Sync +NCIT/ 21-67N activated separately/ 67N&Blocking
Scheme/ Floc&measurement with high harmonic/ Hysteresis at 2% for V> &V<
02/2007
Z1ext+Tilt/ Selfcheck Output board/ NCIT acquisition
Start ∆ & Phase Selection/ Timer&Thermal Protec 5Amp/ KEMA
06/2007
& Floc for 61850-8-1
02/2008 State change & Time stamping
Last C3.x branch version:
03/2008
Phase select & PPGnd fault /DEF & Negative polarisation/ 61850-8-1
New Brand Alstom Grid.
IEC 61850 Phase 1: GOOSE, Non buffered Reports
IEC 61850 9.2 First HW (A)
Improved too early directional decision and Inhibit AR logic
(mandatory upgrade). Versions C3.8 to C3.10: Recommended upgrade.
Full Description of changes
P44x/EN VH/Hb6
(VC) 16-9