Programmable Logic
MiCOM 40 Agile P442, P444
Ordinal
English Text
194
AR Lockout Shot>
195
SG-opto Invalid
196
A/R Fail
197
V<1 Alarm
198
V<2 Alarm
199
V>1 Alarm
200
V>2 Alarm
201
COS Alarm
202
Brok. Cond. Alarm
203
CVT Alarm
204
NCIT Alarm
205
Val/Fail Acq Al.
205
--
206
Test Mode Acq
206
--
207
Synchro Acq Al.
207
--
208
alarm user 1
209
alarm user 2
210
alarm user 3
211
alarm user 4
212
alarm user 5
Description
Autoreclose lockout following final programmed attempt:
Indicates a failed autoreclose (definitive trip following the
last reclosing shot). The relay will be driven to lockout
and the autoreclose function will be disabled until the
lockout condition has been reset. An alarm, "AR Lockout
Shots>" (along with AR Lockout) will be raised.
1 = 'A/R Enable' &
[('1Ptrip & No 'SPAR Enable') + (3P Trip & No 'TPAR
enable)
+ ('1P Trip' + '3P Trip') & (Number of shots=setting)]
Setting group (selected via opto inputs 1 & 2) invalid
No check sync / autorecloser failed: If the check sync
conditions are not met prior to reclosing within the time
window, the 'A/R Fail' alarm will be raised.
1st stage undervoltage alarm picks up when V<1 starts
2nd stage undervoltage alarm picks up when V<21
starts
1st stage overvoltage alarm picks up when V>1 starts
2nd stage overvoltage alarm picks up when V>2 starts
HF carrier anomaly alarm (Carrier out of service)
Broken Conductor Alarm
Alarm for capacitive voltage Transformer: Indicates the
residual voltage is greater than the threshold adjusted in
the settings, during a time-delay greater than the
adjustment. That alarm is also included in the general
alarm.
Relays with IEC 61850 9-2 Ethernet board only
(software version D5.x)
IEC 61850 9-2 Alarm - Frame from Merge Units
missing. If two consecutive of any Logical Node frames
have not been received within the Merge Unit Delay set
parameter (time of silence in the reception of the frame),
the LN is "absent"
Relays with IEC 61850 9-2 Ethernet board only with
software version up to D4.x
Alarm NCIT (9-2 Ethernet) - Frame from Merge Units
failed.
Any Logical Node is synchronized with Internal (local)
synchronization
Unused (software version D5.x)
Relays with IEC 61850 9-2 Ethernet board only with
software version up to D4.x - Any Logical Node is in
"Test Mode"
Unused (software version D5.x)
Relays with IEC 61850 9-2 Ethernet board only with
software version up to D4.x - Any Logical Node is
synchronized with external (global) synchronization
Unused (software version D5.x)
Alarm user for dedicated PSL
Alarm user for dedicated PSL
Alarm user for dedicated PSL
Alarm user for dedicated PSL
Alarm user for dedicated PSL
P44x/EN PL/Hb6
(PL) 6-7
Source
PSL (OUT)
Autorecloser
PSL (OUT)
PSL (OUT)
Autorecloser
PSL (OUT)
V<1
PSL (OUT)
V<2
PSL (OUT)
V>1
PSL (OUT)
V>2
PSL(OUT)
Unblocking
logic
PSL(OUT)
Broken
conductor
PSL (OUT)
PSL (OUT)
PSL (OUT)
PSL (OUT)
PSL (OUT)
PSL(IN)
PSL(IN)
PSL(IN)
PSL(IN)
PSL(IN)