P44x/EN ST/Hb6
(ST) 4-44
Menu Text
CT AND VT RATIOS
Main VT Location
The Check Sync VT may be connected to either a phase to phase or phase to neutral
voltage.
Depending on the particular system arrangement, the main three phase VT for the relay
may be located on either the busbar or the line. Therefore, the relay needs to be
programmed with the location of the main voltage transformer.
CT polarity
Standard or reverse phase sequence can be selected. This menu sets this phase
sequence.
Measured VN *
This setting specifies if the neutral voltage is measured or derived from the sum of three
phase voltages. If this setting is set to Enabled, all function related with synchro-check
function become invisible.
Measured IN *
This setting specifies if the neutral current is measured or derived from the sum of three
phase currents. If this setting is set to Enabled, all function related with Mutual Coupling
become invisible.
3.4
"Record control" column
It is possible to disable the reporting of events from all interfaces that supports setting
changes. The settings that control the various types of events are in the "Record Control"
column. The effect of setting each to disabled is as follows:
This column is visible when the "Record Control" setting ("Configuration" column) = "visible".
Menu Text
RECORD CONTROL
Clear Event
Selecting "Yes" will cause the existing event log to be cleared and an event will be
generated indicating that the events have been erased.
Clear Faults
Selecting "Yes" will cause the existing fault records to be erased from the relay.
Clear Maint.
Selecting "Yes" will cause the existing maintenance records to be erased from the relay.
Alarm Event
Disabling this setting means that all the occurrences that produce an alarm will result in no
event being generated.
Relay O/P Event
Disabling this setting means that no event will be generated for any change in logic input
state.
Opto Input Event
Disabling this setting means that no event will be generated for any change in logic input
state.
Default Setting
Line
Line / Bus
Standard
Standard / Inverted
Disabled
Enabled or Disabled
Disabled
Enabled or Disabled
Default Setting
No
No or Yes
No
No or Yes
No
No or Yes
Enabled
Enabled or Disabled
Enabled
Enabled or Disabled
Enabled
Enabled or Disabled
MiCOM P40 Agile P442, P444
Setting Range
Min.
Max.
Setting Range
Min.
Max.
Setting
Step Size
Step Size