Setting
MiCOM P40 Agile P442, P444
Menu Text
COMMUNICATIONS
Duration of time waited before an inactive tunnel to MiCOM S1 Agile is reset.
NIC Link Report
Configures how a failed/unfitted network link (copper or fiber) is reported:
Alarm - an alarm is raised for a failed link
Event - an event is logged for a failed link
None - nothing reported for a failed link
3.7.5.1
Communications settings for Ethernet port – DNP3.0
Menu Text
COMMUNICATIONS
NIC Protocol
The NIC (Network Interface Cards) protocol cell Indicates that IEC 61850 will be used on
the rear Ethernet port.
IP Address
Indicates the IP (Internet Protocol) address of the rear Ethernet port. This address is
formatted as a six-byte hexadecimal number, and is unique.
Subnet mask
Displays the sub-network that the relay is connected to.
NIC MAC Address
Indicates the MAC (Media Access Control) address of the rear Ethernet port. This address
is formatted as a six-byte hexadecimal number, and is unique.
Gateway
Displays the IP address of the gateway (proxy) that the relay is connected to, if any.
DNP Time Sync
If set to 'Enabled', the DNP3.0 master station can be used to synchronize the time on the
relay. If set to 'Disabled' either the internal free running clock, or IRIG+B input are used.
DNP Meas scaling
Setting to report values in terms of primary, secondary or normalized (with respect to the
CT/VT ratio setting) values.
NIC Tunl Timeout
Duration of time waited before an inactive tunnel to MiCOM S1 Agile is reset.
NIC Link Report
Configures how a failed/unfitted network link (copper or fiber) is reported:
Alarm - an alarm is raised for a failed link
Event - an event is logged for a failed link
None - nothing reported for a failed link
Default Setting
Alarm
Default Setting
DNP3.0
IP Address
Subnet mask
Ethernet MAC Address
Gateway Address
Disabled
Primary
5 mins
Alarm
Setting Range
Min.
Max.
Alarm, Event, None
Setting Range
Min.
Max.
Disabled, Enabled
Primary, secondary or Normalized
1 min
30 mins
Alarm, Event, None
P44x/EN ST/Hb6
(ST) 4-53
Step Size
Step Size
1 min