GE MiCOM P40 Agile Technical Manual page 331

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Programmable Logic
MiCOM 40 Agile P442, P444
Ordinal
English Text
236
Check Synch. OK
237
V< Dead Line
238
V> Live Line
239
V< Dead Bus
240
V> Live Bus
241
Ctrl Cls In Prog
242
DIST Sig. Send
243
DIST UNB CR
244
DIST Fwd
245
DIST Rev
246
DIST Trip A
247
DIST Trip B
248
DIST Trip C
249
DIST Start A
250
DIST Start B
Description
If linked to an opto input in a dedicated PSL and
energised, it indicates that external synchronism
conditions are met – This can be linked afterwards to an
internal autoreclose logic
Dead Line: high when the Dead Line condition is met
(voltage below the 'V< Dead Line' threshold value
(setting) – The measured voltage is always calculated as
a single phase voltage
Live Line: high when the Live line condition is met
(voltage above the 'V> Live Line' threshold value
(setting) - always calculated as a single phase voltage
reference.
Dead Bus: high when the Dead Bus condition is met
(voltage below the V<Dead Bus threshold value (setting)
- always calculated as a single phase voltage reference.
Live Bus: high when the Live Bus condition is met
(voltage above the V>Live Bus threshold value (setting)
- always calculated as a single phase voltage reference.
Manual (control) close in progress - using CB control
(time-delay manual closing delay in progress).
Distance protection schemes - Signal Send (default
PSL: Relay 05)
Unblock main channel received
Internal Carrier Received signal (main Distance
unblocking signal) received.
Distance protection: Forward fault detected (default PSL:
LED6)
Set to 1: Directional Forward detected in distance
algorithms (Deltas or Conventional) AND (Distance
Start)
Set to 0: With reset of Any Start/Dist Start
Distance protection: Reverse fault detected (default
PSL: LED7)
Set to 1: Directional Reverse detected in distance
algorithms (Deltas or Conventional) AND (Distance
Start)
Set to 0: With reset of Any Start/Dist Start
Distance protection: Phase A trip
Set to 0: Reset Dist Trip signal (fixed pulse duration is
80 ms)
Distance protection: Phase B trip
Set to 0: Reset Dist Trip signal (fixed pulse duration is
80 ms)
Distance protection: Phase C trip
Set to 0: Reset Dist Trip signal (fixed pulse duration is
80 ms)
Distance protection started on phase A
Set to 0: Reset of (R, X) (resistance, reactance)
calculation made by All pole Dead detection:
– I Dead: Fourier algorithm calculation (3 or 4 samples
requested)
– V Dead calculated by CB Fail (More than 10ms
requested)
Distance protection started on phase B
Set to 0: Reset of (R, X) (resistance, reactance)
calculation made by All pole Dead detection:
– I Dead: Fourier algorithm calculation (3 or 4 samples
requested)
– V Dead calculated by CB Fail (More than 10 ms
requested)
P44x/EN PL/Hb6
(PL) 6-11
Source
PSL (OUT)
Synchro
Check
PSL (OUT)
Synchro
Check
PSL (OUT)
Synchro
Check
PSL (OUT)
Synchro
Check
PSL (OUT)
Synchro
Check
PSL (OUT)
CB Control
PSL (OUT)
Distance
PSL(OUT)
Unblocking
Logic
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance