GE MiCOM P40 Agile Technical Manual page 370

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P44x/EN PL/Hb6
(PL) 6-50
Ordinal
English Text
1125
SBO DPI2 Org3
1129
SBO DPI2 Org4
1115
SBO InterLock 1
1119
SBO InterLock 2
1123
SBO InterLock 3
1127
SBO InterLock 4
433
SBO Open Org 1
434
SBO Open Org 2
435
SBO Open Org 3
436
SBO Open Org 4
1093
Select CS(NCIT)
195
SG-opto Invalid
312
SOTF Enable
332
SOTF/TOR Trip
1031
SPAR Enable
1083
Stub Bus Enable
207
Synchro Acq Al.
261
T1
1094
T1 Timer Block
Description
SBO support for IEC 61850-8-1 function SBO Double
Point Information 2 Organe 3
SBO support for IEC61850-8-1 function SBO Double
Point Information 2 Organe 4
SBO support for IEC 61850-8-1 control function with
interlocking facilities 1
SBO support for IEC 61850-8-1 control function with
interlocking facilities 2
SBO support for IEC 61850-8-1 control function with
interlocking facilities 3
SBO support for IEC61850-8-1 control function with
interlocking facilities 4
Select Before Operate (SBO) opening function for
organ 1 (interlocking facility in the IEC 60870-5-103
protocol)
Select Before Operate (SBO) opening function for
organ 2 (interlocking facility in the IEC 60870-5-103
protocol)
Select Before Operate (SBO) opening function for
organ 3 (interlocking facility in the IEC60870-5-103
protocol)
Select Before Operate (SBO) opening function for
organ 4 (interlocking facility in the IEC 60870-5-103
protocol)
Select Check synchro for NCIT
Setting group (selected via opto inputs 1 & 2) invalid
Switch On To Fault enabled: Indicates the SOTF logic
is enabled in the relay
Set to 1 =
[SOTF not disabled (Setting 'Distance
schemes /
TOR-SOTF Mode')]
AND
[
{ All poles dead AND (SOTF time-
delay elapsed
(110 s/default)) }
OR
Input Man Close]
OR
(CB control & Close in progress)]
Reset =
500ms time-delay elapsed after Any
pole Dead
OR
Reset of one condition requested for SOTF
enable
Switch on to fault trip or trip on reclose: indicates that a
3-pole trip order has been issued by the TOR or SOTF
logic
Enable internal single pole autorecloser.
Set with Opto input (if linked by PSL) is energized (>
1s).
At 1: 1P AR internal is enabled in the AR logic
At 0: AR 1P internal is disabled (even if set in MiCOM
S1 Agile). AR logic becomes 3P only with AR 3P cycle
-if TPAR =1
Enable I>4 Element for stub bus protection (isolator of
HV line open - status isolator must be connected to an
opto input)
Relays with IEC 61850 9-2 Ethernet board only with
software version up to D4.x - Any Logical Node is
synchronized with external (global) synchronization
Distance time-delay in zone 1 tZ1 elapsed (1 = end of
timer)
If T1=0 picks up when the relay starts (Distance Start
or preset)
Timer block T1 input
Programmable Logic
MiCOM 40 Agile P442, P444
Source
PSL
PSL
PSL
PSL
PSL
PSL
PSL
PSL
PSL
PSL
PSL
PSL (OUT)
PSL (OUT)
SOTF
PSL (OUT)
SOTF
PSL (IN)
Autorecloser
PSL (IN)
PSL (OUT)
PSL (OUT)
Distance
PSL