Distance Algorithms; Distance And Resistance Measurement; Distance And Fault Resistance Estimation - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Application Notes
MiCOM P40 Agile P442, P444
2

DISTANCE ALGORITHMS

The operation is based on the combined use of two types of algorithms:
• "Delta" algorithms, also called High Speed algorithms, using the superimposed current
and voltage values that are characteristic of a fault. These are used for phase
selection and directional determination. The fault distance calculation is performed by
the "impedance measurement algorithms" using Gauss-Seidel.
• "Conventional" algorithms using the impedance values measured while the fault
occurs. These are also used for phase selection and directional determination.
The fault distance calculation is performed by the "impedance measurement
algorithms" using Gauss-Seidel.
The fastest algorithm gives the immediate directional decision.
2.1

Distance and Resistance Measurement

MiCOM P44x distance protection is a full scheme distance relay. To measure the distance
and apparent resistance of a fault, the following equation is solved on the faulted loop:
Z
Local
Source
V
= local terminal relay voltage
L
r = line resistance (ohm/mile)
x =
line reactance (ohm/mile)
I
current flowing in the fault (I + I')
=
F
I
current measured by the relay on the faulty phase
=
current flowing into the fault from local terminal
=
I'
= current flowing into the fault from remote terminal
= fault location (permile or km from relay to the fault)
D
= fault resistance
R
= apparent fault resistance at relay; R x (1 + I'/I)
R
F
Assumed Fault Currents:
For Phase to Ground Faults (ex., A-N),
For Phase to Phase Faults (ex., A-B),
Figure 1: Distance and fault resistance estimation
The impedance measurements are used by High Speed and Conventional Algorithms.
I
L
(n).Z
SL
Relay
V
L
V
= (Z
L
= ((r +jx) x I x D) + R
(1-n).Z
L
L
Relay
R
I
= I + I'
F
F
x I x D) + R
x I
L
F
F
x I
F
F
I
= 3
I
for 40ms, then
F
0
I
I
=
F
AB
P44x/EN AP/Hb6
(AP) 5-11
I
R
Z
SR
V
R
Remote
Source
where
I
after 40 ms
A
P3030ENa