CHAPTER 2: INSTALLATION

Trip1 and Trip2 output relays

345 TRANSFORMER PROTECTION SYSTEM – QUICKSTART GUIDE
Figure 2-19: Control power connection
CONTROL
P P OWER
HEAVY COPPER CONDUCTOR
HEAVY COPPER CONDUCTOR
OR BRAIDED WIRE
OR BRAIDED WIRE
SWITCHGEAR
GROUND BUS
GROUND BUS
The 345 relay is equipped with seven electromechanical relays: two special relays
designed for Winding 1 Breaker trip and Winding 2 Breaker trip, four general purpose
relays (Auxiliary Relays 3 to 6), and a Critical Failure relay. The special purpose relays have
fixed operating characteristics and the general purpose relays can be configured by the
user.
Operation of the two Trip output relays is designed to be controlled by the state of the
circuit breaker as monitored by a 52a or 52b contact.
The Trip relays reset after the breaker is detected in a state corresponding to the
command. When a relay feature sends a command to one of these special relays, it
will remain operational until the requested change of breaker state is confirmed by a
breaker auxiliary contact and the initiating condition has reset.
If the initiating feature resets, but the breaker does not change state, the output relay
will be reset after a default interval of 2 seconds.
If neither of the breaker auxiliary contacts, 52a nor 52b, is programmed to a contact
input, the Trip Relay is de-energized after either the delay programmed in the Breaker
Failure feature, or a default interval of 100 ms after the initiating input resets.
If a delay is programmed for the Trip contact seal-in time, then this delay is added to
the reset time. Note that the default setting for the seal-in time is 40 ms.
52a Contact
52b Contact
Configured
Configured
Yes
Yes
Yes
No
No
Yes
No
No
+
-
B2
A1
B1
-
+
CONTROL
POWER
Relay Operation
Trip Relay remains operational until 52b indicates an
open breaker.
Trip Relay remains operational until 52a indicates an
open breaker.
Trip Relay remains operational until 52b indicates an
open breaker.
Trip Relay operates until either the Breaker Failure delay
expires (if the Breaker Failure element is enabled), or 100
ms after the feature causing the trip resets.
ELECTRICAL INSTALLATION
RELAY
898735.CDR
898735.CDR
31