Programmable Logic
MiCOM 40 Agile P442, P444
Ordinal
English Text
177
VT Fail Alarm
337
VTS Fast
266
WI Trip A
267
WI Trip B
268
WI Trip C
255
Z1
349
Z1 Not Filtrated
256
Z1X
1053
Z1X Extension
257
Z2
258
Z3
259
Z4
260
Zp
394
Zq
347
ZSP Start
1087
ZSP Timer Block
348
ZSP Trip
454
LBlinder DetectAN
Description
Fuse failure indication (VT alarm). High when the opto
input is energised (copy of MCB) OR an internal Fuse
Failure is confirmed when the VTS timer elapses.
Instantaneous unconfirmed fuse failure internal
detection. Set high for internal Fuse Failure detection
made with internal logic.
Phase A trip on weak infeed
Phase B trip on weak infeed
Phase C trip on weak infeed
Fault in zone 1 (convergence of loop in Z1)
Set to 0: Reset of (R, X) (resistance, reactance)
calculation made by All pole Dead detection
(default PSL: LED 5, Relays 01 / 10)
Z1 decision not filtered by phase selection
Fault in zone 1 extended Z1x (convergence of loop in
Z1x) and filtered by blocking/unblocking Power
Swing/Reversal guard logic (default PSL: LED 5, Relay
10)
Zone 1 Extension Input
Opto input energized if linked by PSL OR any internal
DDB by dedicated PSL
At 1: Signal will initiate Z1 extension logic if selected
(setting).
This DDB can be assigned to any external/Internal
condition for starting Z1X logic
Fault in zone 2 (convergence of loop in Z2) and filtered
by blocking/unblocking Power Swing/Reversal guard
logic
logic (default PSL: LED 5, Relay 10)
Fault in zone 3 (convergence of loop in Z3) and filtered
by blocking/unblocking Power Swing/Reversal guard
logic
logic (default PSL: LED 5, Relay 10)
Fault in zone 4 (convergence of loop in Z4) and filtered
by blocking/unblocking Power Swing/Reversal guard
logic
logic (default PSL: LED 5, Relay 10)
Fault in zone P Zp (convergence of loop in Zp)
logic (default PSL: LED 5, Relay 10)
Fault in zone Q
Zero Sequence Power - Start: The ZSP START cell at
1 indicates the Zero Sequence Power function has
started - in the same time, it indicates the timer-delays
associated have started and are running (fixed one first
and then IDMT timer)
Zero Sequence Power - Timer Block: If assigned to an
opto input in a dedicated PSL, Zero Sequence Power
function will start, but will not perform a trip command -
the associated time-delay (adjusted with 'K Time Delay
Factor ' setting, will be blocked
Zero Sequence Power - Trip: The ZSP TRIP cell at 1
indicates the Zero Sequence Power function has
performed a trip command (after the start and when
associated timers are issued)
Load Blinder Detection in Loop AN: Cell at 1 indicates
the Impedance is located within the AN loop Load
Blinder Region.
P44x/EN PL/Hb6
(PL) 6-55
Source
PSL (OUT)
VT
Supervision
PSL (OUT)
VTS
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
PSL (OUT)
Distance
PSL (IN)
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL
PSL (OUT)
ZSP
PSL (IN)
ZSP
PSL (OUT)
ZSP
PSL (OUT)
Distance