Autoreclose Force Sync; Cb Discrepancy; No Pick-Up At The End Of The Dead Time; Check Sync Signal Will Be Forced At The End Of Dead Time - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P44x/EN AP/Hb6
(AP) 5-158
• When "autoreclose Lockout / Block A/R" is enabled, the autoreclose does not initiate
any additional A/R cycle. If the autorecloser locks out during a cycle, 'A/R close' is
blocked.
• A dedicated PSL can be created for performing an autoreclose lockout in case of
confirmed Fuse Failure.

5.10.1.8 Autoreclose force Sync

The DDB: 'A/R Force Sync' forces synchronism check to be made.
It simulates the check synchronisation control and forces the logical DDB output
'CheckSync OK' at 1 during a 1 pole or 3 poles high speed AR cycle.
Figure 120: No pick-up at the end of the dead time
Figure 121: Check sync signal will be forced at the end of dead time

5.10.1.9 CB Discrepancy

The DDB: 'CB Discrepancy' signal informs the protection of a pole discrepancy status (one
pole opened and the other two poles closed). It must be set to high logical level before Dead
time 1 has elapsed – it can also be generated internally (see Cbaux logic).
Figure 122: Pole discrepancy (CBA-Disc)