Default Simulation Principle; To Simulate A Single-Phase Fault; Characteristic Point Determination - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Commissioning
MiCOM P40 Agile P442, P444
5.3.1.2

Default simulation principle

To simulate a single-phase fault

The distance protection detects a single-phase default in E if the impedance and phase of
this point place it inside the characteristic. The relation between the impedance and phase
and the injected voltage and current is as follows:
• Fault Impedance Z = Vphase/Iphase;
• Fault Phase ϕ = phase-shift(Vphase, Iphase) ;
• The Vphase voltage has to remain lower than the rated voltage value
Impedance test for zone 1:
I1
= 1A
ϕ1
= line angle = 76°
V
1
= Zfault = Zd (1 + k0) + Rfault
I
1
Rfault = R loop
Figure 7:
Characteristic point determination (Rlim two-phase & Single-phase can be
different)
The characteristic angle is:
• For phase-to-phase: Argument of the positive impedance of the line (Z1)
• For phase-to-earth: Argument of 2Z1+Z0
The relay characteristic can be created and displayed with Z-Graph (MiCOM Z-Graph
software is a tool delivered with the protection)
Distance X
Xlim
-Rlim
E
j
Resistance R
Rlim
P44x/EN CM/Hb6
(CM) 9-25
P3017ENa