P44x/EN SC/Hb6
(SC) 12-14

Working offline:

1.
Click the icon New MiCOM Configuration from an Installed ICD File.
2.
Double-click the product variant.
3.
Double-click the Communications item.

Or working online:

1.
Select Device > Manage IED.
2.
Select the IED type device number.
3.
Select the IED address and click Next. The IED 61850 Configurator tool reads
information from the IED and shows them in the Summary view.
4.
Click the Communications tab to read and edit the settings.
Then:
1.
The Media setting defines the default interface used to communicate between
clients and peers, and the MiCOM IED. The value is taken from the
ConnectedAP/PhysConn section of the configured SCL file and is editable in
Manual Editing Mode. The single Ethernet board has one fibre and one copper
interface. If you are using fibre, select Single Fibre. If you are using copper, select
Single Copper or Redundant Fibre. If you are using a Redundant Ethernet board,
select Single Copper or Redundant Fibre.
2.
Set the Ethernet Failover to Enable and adjust the Failover Timeout as required.
This does not appear if the product does not have Ethernet Failover.
SCADA Communications
MiCOM P40 Agile P442, P444