GE MiCOM P40 Agile Technical Manual page 90

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P44x/EN ST/Hb6
(ST) 4-16
Menu text
GROUP 1 – DISTANCE ELEMENTS
OTHER PARAMETERS
Serial Cmp.line
Serial Compensated Line: If enabled, the Directional Line used in the Delta Algorithms is set
at 90° (Fwd = Quad1&4 / Rev = Quad 2&3).
If disabled, the Directional Line of the Delta algorithms is set at -30° like conventional
algorithms.
Overlap Z Mode
Overlap Z Mode: If enabled, for a fault in Zp (fwd), then Z1 & Z2 will be displayed in
LCD/Events/Drec – The internal logic is not modified.
Z1m Tilt Angle
Z1p Tilt Angle
The settings dealing with the tilt ('Z1m Tilt Angle', 'Z1p Tilt Angle', 'Z2p/Zp/Zq Tilt Angle')
and the evolving forward zone detection to zone1 (to avoid a Z1 detection in case of
impedance locus getting out from the quad, due to remote CB operating) but crossing the
Z1 before being out from the quad (with enough points that a Z1 decision) can be confirmed
if that timer has been set to 0ms.
Z1m and Z1p Tilt Angle: The tilt angles can be independently set (±45°) for phase-to-ground
and phase-to-phase setting.
Z2/Zp/Zq Tilt Angle
Tilt characteristic for zone 2, zone P and zone Q (common setting for phase-to-ground and
phase-to-phase).
Fwd Z Chgt Delay
This time delay is set to prevent maloperation due to zone evolution from zone
by CB operation.
Default setting
Disable
Enable
X
REV
REV
X
FWD
REV
Disable
Enable
-45°
-45°
-45°
30ms
0
MiCOM P40 Agile P442, P444
Setting range
Min
Max
Disable
FWD
R
FWD
P0472EN
FWD
R
FWD
REV
-30°
P0473EN
Disable
45°
45°
45°
100ms
Setting
Step size
1ms
to zone
n
n-1