GE MiCOM P40 Agile Technical Manual page 83

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Setting
MiCOM P40 Agile P442, P444
Menu text
CONFIGURATION
Thermal Overload
To enable (activate) or disable (turn off) the thermal overload protection function.
I< Protection
To enable (activate) or disable (turn off) the Undercurrent protection function.
Residual O/V NVD
To enable (activate) or disable (turn off) the Residual overvoltage protection function.
Freq protection
To enable (activate) or disable (turn off) the Frequency protection (under / overfrequency)
function.
Internal A/R
Internal Autoreclose: Should autoreclosure not be required, the function may be Disabled.
Disabling the autorecloser does not prevent the use of the internal check synchronism
element to supervise manual circuit breaker closing. If the autoreclose function is Enabled,
the setting guidelines (autoreclose section) should be read.
Input Labels
To the Input Labels menu visible or invisible in the relay menu settings menu.
Output Labels
To the output Labels menu visible or invisible in the relay menu settings menu.
CT & VT Ratios
Sets the Current and Voltage Transformer ratios menu visible.
Record Control
Sets the record control menu visible or invisible.
Disturb Recorder
Sets the disturbance recorder menu visible or invisible.
Measure't Setup
Sets the measurement setup menu visible or invisible.
Comms Settings
Sets the communications settings menu visible or invisible.
Commission Tests
Sets the commission tests menu visible or invisible.
Setting Values
This affects all protection settings that are dependent on CT and VT ratios. All subsequent
settings input must be based in terms of this reference.
Control Inputs
Activates the Control Input status and operation menu further on in the relay setting menu.
Ctrl I/P Config
Sets the Control Input Configuration menu visible further on in the relay setting menu.
Ctrl I/P Labels
Sets the Control Input labels menu visible further on in the relay setting menu.
Default setting
Disabled
Enabled or Disabled
Disabled
Enabled or Disabled
Disabled
Enabled or Disabled
Disabled
Enabled or Disabled
Disabled
Enabled or Disabled
Visible
Invisible or Visible
Visible
Invisible or Visible
Visible
Invisible or Visible
Invisible
Invisible or Visible
Invisible
Invisible or Visible
Invisible
Invisible or Visible
Visible
Invisible or Visible
Visible
Invisible or Visible
Primary
Primary or Secondary
Visible
Invisible or Visible
Visible
Invisible or Visible
Visible
Invisible or Visible
P44x/EN ST/Hb6
(ST) 4-9
Available settings

Advertisement

Table of Contents
loading

This manual is also suitable for:

P442P444

Table of Contents