S3: Output Relays - GE 239 Instruction Manual

Multilin motor protection relay
Hide thumbs Also See for 239:
Table of Contents

Advertisement

4 PROGRAMMING
SETPOINT
]] SETPOINTS
]] S3 OUTPUT RELAYS
MESSAGE
MESSAGE
] TRIP RELAY
]
MESSAGE
MESSAGE
] ALARM RELAY
]
MESSAGE
MESSAGE
] AUXILIARY RELAY
]
MESSAGE
MESSAGE
] END OF PAGE S3
]
NON-FAILSAFE: The relay coil is not energized in its non-active state. Loss of control power will
cause the relay to remain in the non-active state; i.e. a non-failsafe alarm or trip
relay will not cause an alarm or trip on loss of control power. Contact configura-
tion is shown in Figure 2–3: TYPICAL WIRING DIAGRAM on page 2–4 with
relays programmed non-failsafe, control power not applied
FAILSAFE: The relay coil is energized in its non-active state. Loss of control power will cause
the relay to go into its active state; i.e. a failsafe alarm or trip relay will cause an
alarm or trip on loss of control power. Contact configuration is opposite to that shown
in Figure 2–3: TYPICAL WIRING DIAGRAM on page 2–4 for relays programmed as
failsafe when control power is applied
GE Multilin
Courtesy of NationalSwitchgear.com
SETPOINT
4
MESSAGE
TRIP OPERATION:
NON-FAILSAFE
3
MESSAGE
4
MESSAGE
ALARM OPERATION:
NON-FAILSAFE
3
MESSAGE
4
MESSAGE
AUXILIARY OPERATION:
NON-FAILSAFE
3
MESSAGE
Figure 4–4: SETPOINTS PAGE 3 – OUTPUT RELAYS
239 Motor Protection Relay
]] SETPOINTS
]] S4 PROTECTION
Range: NON-FAILSAFE, FAILSAFE
Range: NON-FAILSAFE, FAILSAFE
ALARM ACTIVATION:
UNLATCHED
Range: NON-FAILSAFE, FAILSAFE
AUXILIARY ACTIVATION:
UNLATCHED
AUXILIARY FUNCTION:
NORMAL
4 PROGRAMMING

4.4 S3: OUTPUT RELAYS

Range: LATCHED, UNLATCHED
Range: UNLATCHED, LATCHED
Range: NORMAL, TRIPS, ALARMS
4
4-13