Table 6 - Relay Output Terminals and Test Pattern Settings
Return the relay to service by setting cell [0F0E: COMMISSIONING TESTS, Test Mode] to
'Disabled'.
4.2.9

Rear Communications Port

This test should only be performed where the relay is to be accessed from a remote location
and will vary depending on the communications standard being adopted.
It is not the intention of the test to verify the operation of the complete system from the relay
to the remote location, just the relay's rear communications port and any protocol converter
necessary.
4.2.9.1

Courier Communications

If a K-Bus to RS232 KITZ protocol converter is installed, connect a portable PC running the
appropriate software to the incoming (remote from relay) side of the protocol converter.
If a KITZ protocol converter is not installed, it may not be possible to connect the PC to the
type installed. In this case a KITZ protocol converter and portable PC running appropriate
software should be temporarily connected to the relay's K-Bus port. The terminal numbers
for the relay's K-Bus port are given in Table 7. However, as the installed protocol converter
is not being used in the test, only the correct operation of the relay's K-Bus port will be
confirmed.
Connection
K-Bus
Screen
1
2
Table 7 - RS485 Terminals
Ensure the communications baud rate and parity settings in the application software are set
the same as those on the protocol converter (usually a KITZ but could be a SCADA RTU).
The relay's Courier address in cell [0E02: COMMUNICATIONS, Remote Address] must be
set to a value between 0 and 255.
Check that communications can be established with this relay using the portable PC.
M5-M6
M7-M8
M9-M10
M11-M12
M14-M15
M17-M18
L3(–)-L4(+)
L7(–)-L8(+)
L11(–)-L12(+)
L15(–)-L16(+)
K3(–)-K4(+)
K7(–)-K8(+)
K11(–)-K12(+)
K15(–)-K16(+)
J3(–)-J4(+)
Modbus or VDEW
Screen
+ve
–ve
MiCOM P40 Agile P442, P444
HB relay 20
-
Relay 21
-
Relay 22
-
Relay 23
-
Relay 24
H7-H9
Relay 25
H10-H12
Relay 26
H13-H15
Relay 27
H16-H18
Relay 28
-
Relay 29
-
Relay 30
-
Relay 31
G7-G9
Relay 32
G10-G12
Relay 33
G13-G15
Relay 34
G16-G18
Terminal
P442
P444
J16
N16
J17
N17
J18
N18
Commissioning
J15(–)-J16(+)
H1-H2
H3-H4
H5-H6
H8-H9
H11-H12
H14-H15
H17-H18
G1-G2
G3-G4
G5-G6
G8-G9
G11-G12
G14-G15
G17-G18