Security Configuration ("Security Config" Menu, If Option Avalable) - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P44x/EN ST/Hb6
(ST) 4-70
3.18

Security configuration ("SECURITY CONFIG" menu, if option avalable)

The SECURITY CONFIG column contains the main configuration settings for Security
functions. This column is used to set the password attempts number and duration. When
these limits expire, access to the interface is blocked until timer has expired. This setting
enables or disables port access.
Menu Text
SECURITY CONFIG
ACCESS ONLY FOR AUTHORISED USERS
Attempts Limit
Adjust the number of attempts to enter a valid password. When the maximum number of
attempts has been reached, access is blocked.
Attempts Timer
Adjust the time limit (minutes) to enter the correct password.
Blocking Timer
Adjust the blocking timer (minutes) after a password blocking. Once the password is
blocked, this blocking timer is initiated. Only after the blocking timer has expired will
access to the interface be unblocked, where on the attempts counter is reset to zero.
Front Port
Enable or disable the front port access. A level 3 password is needed to perform this
action. To prevent accidental disabling of a port, a warning message "FRONT PORT TO
BE DISABLED, CONFIRM" is required to be disabled.
Rear Port 1
Enable or disable the rear port 1 access. A level 3 password is needed to perform this
action. To prevent accidental disabling of a port, a warning message "REAR PORT 1 TO
BE DISABLED, CONFIRM" is required to be disabled.
Rear Port 2
When fitted, enable or disable the rear port 2 access. A level 3 password is needed to
perform this action. To prevent accidental disabling of a port, a warning message "REAR
PORT 2 TO BE DISABLED, CONFIRM" is required to be disabled.
Ethernet Port
When fitted, enable or disable the Ethernet port access. A level 3 password is needed to
perform this action. To prevent accidental disabling of a port, a warning message
"ETHERNET TO BE DISABLED, CONFIRM" is required to be disabled.
Caution: disabling the Ethernet port disables all Ethernet based communications.
Courier Tunnel
Enable or disable the Courier tunneling logical port access. A level 3 password is needed
to perform this action.
Note: if this protocol is enabled or disabled, the Ethernet card reboots.
IEC61850
Enable or disable the IEC61850 logical port access. A level 3 password is needed to
perform this action.
Note: if this protocol is enabled or disabled, the Ethernet card reboots.
DNP3 OE
Enable or disable the DNP3 logical port access. A level 3 password is needed to perform
this action.
Note: if this protocol is enabled or disabled, the Ethernet card reboots.
Default Setting
2
0
2
1
5
1
Enabled
Enabled or Disabled
Enabled
Enabled or Disabled
Enabled
Enabled or Disabled
Enabled
Enabled or Disabled
Enabled
Enabled or Disabled
Enabled
Enabled or Disabled
Enabled
Enabled or Disabled
MiCOM P40 Agile P442, P444
Setting Range
Min.
Max.
3
3
30
Setting
Step Size
1
1
1