6 Commissioning
6.3

Series commissioning

An existing parameter set can be transferred to a MICROMASTER 420 frequency
inverter using STARTER or DriveMonitor (refer to Section 4.1 "Establishing
communications MICROMASTER 420 ⇔ STARTER").
Typical applications for series commissioning include:
1. If several drives are to be commissioned that have the same configuration and
same functions. A quick / application commissioning (first commissioning) must
be carried-out for the first drive. Its parameter values are then transferred to the
other drives.
2. When replacing MICROMASTER 420 frequency inverters.
6.4

Parameter reset of factory setting

START
Commissioning parameter
P0010=30
30
Factory setting
Factory reset
P0970 = 1
0
disabled
1
Parameter reset
The drive inverter carries-out a parameter reset (duration, approx. 10 s) and then
automatically exits the reset menu and sets:
P0970 = 0 :
P0010 = 0 :
END
26
disabled
ready
Issue 04/04
0
0
MICROMASTER 420
Compact Operating Manual