Technical Data
4.1 General
4.1.4
Communication Interfaces
Protection data interfaces
See Section 4.2 „Protection Data Interfaces and Communication Topology"
Operator Interface
Connection
Operation
Transmission rate
Transmission distance
Service/Modem Interface (optional)
RS232/RS485
RS232
RS485
326
Front side, non-isolated, RS232,
9-pin D-subminiature female connector for connection of a PC
With DIGSI
Min. 4800 Baud; max. 115200 Baud;
Factory Setting: 38400 Baud; Parity: 8E1
15 m / 50 feet
RS232/RS485/FO
Acc. to ordered version
Operation
Connection for flush mounting housing
For Panel Surface-Mounted Case
Test Voltage
transmission rate
Maximum Distance of Transmission
Maximum Distance of Transmission
Isolatede interface
for data transfer
with DIGSI
RS232/RS485 according to ordered variant
Rear panel, mounting location „C",
9-pole D-subminiature female connector
Shielded data cable
Shielded data cable
at the terminal
at the case bottom
in console housing
at the case bottom;
9-pole D-subminiature female connector
500 V; 50 Hz
Min. 4800 Baud; max. 115200 Baud
Factory setting 38400 Baud
15 m (50 ft)
1,000 m (3280 ft)
SIPROTEC, 7SD610, Manual