Safety, approvals, EMC

10.2 Test voltages

10.2
Test voltages
Figure 10-1
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
● Connect the input terminals with one another
● Connect the output terminals with PE
Test (C)
● Connect the output terminals with one another and measure with respect to PE
Table 10- 1
Test voltage
Type test
Production test
Field test
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: < 100 mA
300
Test voltage without auxiliary contact diagram
Test time
Prim ↔ sec (A)
60 s
4200 V DC
60 s
3000 V AC
1 s
2200 V DC
1 s
1500 V AC
1 s
2200 V DC
1 s
1500 V AC
Prim ↔ PE (B)
Sec ↔ PE (C)
2200 V DC
707 V DC
1500 V AC
500 V AC
2200 V DC
860 V DC
1500 V AC
600 V AC
2200 V DC
500 V DC
1500 V AC
350 V AC
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76