Data
Soft Output
Characteristics Output
1 (0/255)
Ithreshold (0-100%)
Fill byte(s)
Device input voltage
[10mV]
Device output current
[10mA]
Device operating state
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76
Description
switched on in a fixed
sequence 1, 2,...n with an
identical delay time be-
tween the outputs. For a
variable switch-on delay,
each output uses an indi-
vidually specified delay
time based on a common
starting point.
Soft output characteristic of output 1 of the SITOP PSU8600 is activated.
Prewarning threshold for the actual system power, referred to the rated power
of the power supply system.
-
Input voltage: rms value of the supply voltage at the input of the
SITOP PSU8600.
System load current: Sum of the actual load currents of all outputs of the power
supply system.
Operating state
2 =
100 ms switch on delay
StartupDelay100ms
Outputs are switched on
in an ascending sequence
(starting with output 1 of
the basic device) in inter-
vals of 100 ms.
3 = StartupDelay
Load-optimized switch on
LoadOptimized
delay: Outputs are
switched on in an ascend-
ing sequence (starting
with output 1 of the basic
device) in a load-
optimized fashion.
4 = StartupDelay
Variable switch on delay:
Variable
Depending on the param-
eterized delay time, out-
puts are activated after
the supply voltage is
switched on.
0 = Off
Power supply system is
switched off
1 = ErrorOff
The power supply system
was automatically shut
down as a result of opera-
tion under inadmissible
operating conditions.
2 = ReadyForRestart
After an automatic shut-
down due to a fault, the
power supply system can
be reactivated by switch-
ing off and switching on
the supply voltage.
3 = Boot
The power supply system
is powering up, all of the
outputs are still switched
off.
4 = Running
The power supply system
is operating in the normal
mode.
Engineering and remote access
7.6 Cyclic and acyclic data
Data type
Unsigned8
Unsigned8
Unsigned16
Unsigned16
Unsigned16
Unsigned8