Description, device design, dimension drawing
2.3 Description of the buffer modules
Table 2- 3
Designation
4 s/40 A buffer module
10 s/40 A buffer module
...
When the buffer module with double-layer capacitors is completely charged (LED "OK" lights
green) power failures of 4 s or 10 s can be buffered with a load current of 40 A. The buffer
time is correspondingly increased for lower load currents.
20
BUF8600 buffer modules with double-layer capacitors
Buffer time
4 s at 40 A
10 s at 40 A
Connecting plug at the upper side of the device for plug connection to the basic device or
to additional modules
Socket at the upper side of the device for the plug connection to additional modules
"O.K." LED
Remote ON/OFF and signaling contacts
DIN rail slider
Convection
Clearance above/below
Charge time for a rated
input voltage of 400 V
typ. 5 min;
max. 8 min
(when completely dis-
charged)
typ. 10 min;
max. 18 min
(when completely dis-
charged)