Engineering and remote access
7.6 Cyclic and acyclic data
7.6.2.4

Data sets SITOP BUF8600

Index 6: Device information (reading)
Data
MLFB/Order number
Product state
Fill byte(s)
SW version
Serial number
Index 32: State information (reading)
SITOP BUF8600 100 ms/40 A and SITOP BUF8600 300 ms/40 A
Data
Fill byte(s)
Fill byte(s)
Charging current
[10mA]
Load current [10mA]
Module operation state Operating state
196
Description
-
-
Charge current
not supported (always 0)
Load current
not supported (always 0)
Description
Article No./Order number
Product release
-
Software version
Serial number
0 = Off
Buffer component is in the
"Off" operating state.
1 = Boot
Buffer component is pow-
ering up.
2 = Full
Complete buffer readi-
ness: The energy storage
device of the buffer com-
ponent is fully charged
(normal operation).
3 = Buffering
The buffer component is
operating in the buffer
mode: The power supply
system is supplied via the
buffer component(s).
4 = ErrorOff
Shutdown after an error:
A fault/error has occurred
when operating the buffer
component. The buffer
component is not opera-
tional and must be re-
started by switching off
the supply voltage and
switching it on again.
Data type
VisibleString(20)
Unsigned8
Unsigned8
Unsigned32
VisibleString(16)
Data type
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned8
Power supply system PSU8600
Manual, 05.2017, A5E36758446-3-76